The Bacharach MGS-460 is a robust refrigerant gas detector with a remote sensor head, designed for installation in hard-to-reach areas. Featuring Modbus RTU, analogue outputs, three relays, and an IP66 enclosure, it simplifies compliance with EN 378 and ASHRAE 15 in machinery rooms, cold stores, and freezers.
Bacharach MGS-460 Gas DetectorThe Bacharach MGS-460 Gas Detector extends the flexibility of the MGS-400 series by incorporating a remote sensor head, allowing gas detection in confined or hard-to-reach spaces while maintaining a convenient interface point for wiring and communication.
Engineered for refrigeration safety, the MGS-460 supports a wide range of gases including halogenated refrigerants, CO₂, NH₃, O₂, CO, hydrocarbons (R-290, R-600) and NO₂. Pre-calibrated, plug-and-play sensor modules make replacement quick, with no need for calibration gas or specialist tools.
The unit combines digital (Modbus RTU) and analogue (configurable 4–20 mA/voltage) outputs for seamless integration into building management systems, refrigeration controls, or the Bacharach MGS-408 controller. Three onboard relays provide local control of fans, strobes, or shutdown equipment, while integrated audio/visual alarms ensure immediate local notification.
Its IP66 enclosure and low-temperature performance down to -40 °C make it ideal for machinery rooms, chiller plants, walk-in freezers, and other demanding environments. With support for Bluetooth app configuration, the MGS-460 offers a user-friendly, modern solution for achieving compliance with EN 378 and F-Gas Regulation while reducing downtime and maintenance costs.
Key Features
Remote Sensor Capability: Detect refrigerants in confined or inaccessible areas.
Analogue & Digital Outputs: 4–20 mA/voltage + Modbus RTU via RS-485.
Onboard Relays: Three SPDT relays for alarms, fault indication, or equipment control.
Integrated A/V Alarms: LED and buzzer comply with ASHRAE 15 / EN 378.
IP66 Enclosure: Built to withstand dust, moisture, and harsh environments.
Low-Temperature Performance: Operates reliably down to -40 °C.
Plug-and-Play Sensors: Pre-calibrated modules simplify installation and service.
Mobile App Support: Easy commissioning and maintenance via the MGS-400 app.
Gases and Ranges
Refrigerants: 1,000 ppm
CO₂: 5,000 / 10,000 / 20,000 / 30,000 / 40,000 / 50,000 ppm
NH₃: 100 / 1,000 / 5,000 / 100% LEL
O₂: 30 Vol%
CO: 500 ppm
Combustible gases – Semiconductor (R-290, R-600, R-50, R-600a, HC-12a, R-717): 5,000 ppm
Combustible gases – NDIR (R-600, R-50, R-290): 100% LEL
Combustible gases – Catalytic (R-600, R-50, R-290, R-717): 100% LEL
NO₂: 20 ppm
Status Indicator
Single tri-color LED (green, red, orange)
Buzzer
72 dB @ 10 cm
Output
Analog: Single configurable output (4–20 mA, 0–5 V, 0–10 V, 1–5 V, 2–10 V)
Digital: Modbus RTU via RS-485
Power Supply
24 V AC or DC (auto selecting), 4 W (max)
Relay
Three SPDT relays, fixed low / high / fault alarms
Rating: 1 A @ 30 VDC
Enclosure
IP66
Size (W × H × D)
General purpose (base): 6.5 × 6.5 × 3.4 in (165 × 165 × 87 mm)
Remote head: 4.5 × 5.4 × 2.7 in (115 × 136 × 68 mm)
Weight
Approx. 1 lb 11.7 oz (758 g)
Approvals
CE, UL / CSA, IEC EN 61010-1
Ambient Conditions
Temperature
Semiconductor: -40 to +122 °F / -40 to +50 °C
Electrochemical:
– NH₃ 100 / 1,000 ppm: -40 to +40 °C
– NH₃ 5,000 ppm: -20 to +40 °C
– CO 500 ppm: -40 to +50 °C
– NO₂ 20 ppm: -20 to +40 °C
– O₂ 30% Vol: -20 to +50 °C
Infrared: -40 to +122 °F / -40 to +50 °C
Catalytic Bead: -40 to +122 °F / -40 to +50 °C
Humidity
5 to 90 % RH, non-condensing
Pressure
23.6 to 32.5 in Hg / 800 to 1,100 mbar