The Crowcon BESafe™ Dual Channel Gas Detector is a compact gas monitoring solution engineered for battery energy storage systems (BESS). It simultaneously detects hydrogen (H₂), carbon monoxide (CO), and methane (CH₄).
Crowcon BESafe Dual Channel Gas DetectorThe Crowcon BESafe™ Dual Channel Gas Detector is a high-performance, fixed gas detection solution for battery energy storage systems (BESS) and critical backup infrastructure. With the ability to monitor two gases simultaneously – hydrogen (H₂), carbon monoxide (CO) or methane (CH₄), BESafe offers early warning against thermal runaway events, battery off-gassing, and fire risks. Its compact form factor fits neatly into confined spaces such as energy storage enclosures, inverter rooms, or UPS cabinets, while rugged IP65-rated construction ensures reliable operation in harsh environments.
Equipped with modular, smart sensors that are pre-calibrated and swappable on-site, BESafe minimises maintenance downtime and eliminates manufacturer intervention. The integrated sensor life indicator and non-intrusive testing capabilities deliver consistent performance with minimal disruption to operations. Visual and audible alarms, including an 85dB sounder and multi-color LED indicators—provide immediate awareness of hazardous gas levels. In addition, multiple signal output options (including 4–20mA, RS-485 Modbus RTU, and SPDT relays) allow seamless integration into existing building management, SCADA, or safety systems.
With its OLED display for precise gas readings in all lighting conditions and built-in support for automatic control of external devices like fans or alarms, BESafe enhances safety and compliance in high-risk battery storage environments. Ideal for utility-scale BESS, EV charging infrastructure, data centres, and industrial hydrogen facilities. BESafe is the frontline technology for detecting critical gases associated with lithium-ion battery degradation and thermal failure.
Key Features
Dual gas detection
Swappable sensors
Multiple signal output
Compact and flexible design
On-site, built-in alarm functions
Size
175 x 150 x 55mm
Weight
Base: 550g
Adapter: 169g
Sensor Tray: 65g each
Enclosure Material
Polycarbonate
Ingress Protection
IP65
Cable Entry
M20
Power
10 to 30V DC, 24V DC Nominal
150mA (3.6W @ 24V dc), 5W Max
Display
128×64 OLED
Electrical Output
2 x 4-20mA
RS-485 Modbus RTU
Relays Output
SPDT Relay (1A at 24 VDC)
Alarm 1, Alarm 2, Fault
Audio Visual Output
Sounder: 85dB @ 3m
LED: Power (Green), Fault (Yellow), Alarm (Red)
Operating Temperature
CE: -20 to +60°C
UL: -20 to +50°C
Operating Humidity
0 to 99% RH (non-condensing)
Data Logging
3000 data logs
Approvals
EN 61010-1
EN 50270
UL 2075
Warranty
2 years on Transmitter and Sensors
Sensor
Gas
Range
Temperature Range
Catalytic
Hydrogen
Methane
0-25% LEL
0-100% LEL
-20°C
Electrochemical
Carbon Monoxide
0-1000ppm
-20°C to +50°C